Datasheet
11/30/2015 167880 - HPL-ED2015 V17.0 EN 2 / 4
Max. switching duty (resistive load) W 60
Max. switching voltage AC V 240
Max. switching voltage DC V 220
Maximum switching current A 2
Min. switching capacity (reference value) 10 μA, 10 mV DC
lifespan
Electrical (at 20 switching operations per minute) 2 A 30 VDC resistive load Operations
>10
5
Electrical (at 20 switching operations per minute) 1 A 30 VDC resistive load Operations
>5 x 10
5
Terminal capacity mm² 0.25 - 1.5
Mechanical
Standard front dimension mm 45
Device height mm 80
Built-in width mm 70 (4TE)
Mounting Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of Protection IP20 switches
IP 40 enclosed
Terminals top and bottom Twin-purpose terminals
Terminal protection Busbar tag shroud to BGV A3, ÖVE-EN 6
Terminal cross-section
Solid
mm
2
1.5 - 35
Stranded
mm
2
2 x 16
Terminal cross-section M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, Pozidriv PZ2)
Tightening torque of fixing screws N/m 2 - 2.4
Thickness of busbar material mm 0.8 - 2
Admissible ambient temperature range °C -25 - +55
Permissible storage and transport temperatures °C -35 - +60
Climatic proofing according to IEC/EN 61008
Mounting position As required
Contact position indicator red / green
Trip indication white / blue
Design�verification�as�per�IEC/EN�61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 25
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 4.6
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
0
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.