Cut Sheet
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Technical Data
29-620
Page 4
October 1997
Printed in U.S.A.
FDPW Switch Ratings
Ampere Voltage Short Circuit Horsepower Rating Fuse Size and Type of Cu/Al
Rating Rating Type Conductor Per Phase
30A 240V Ac 200 kAIC 3 7.5 R
Switch 480V Ac 200 kAIC 5 15 R, J
600V Ac 200 kAIC 7.5 20 R, J
250V Dc 10 kAIC 5 5 ➀
60A 240V Ac 200 kAIC 7.5 15 R
Switch 480V Ac 200 kAIC 15 30 R, J
600V Ac 200 kAIC 15 50 R, J
250V Dc 10 kAIC 10 10 ➀
100A 240V Ac 200 kAIC 15 30 R
Switch 480V Ac 200 kAIC 25 60 R, J
600V Ac 200 kAIC 30 75 R, J
250V Dc 10 kAIC 20 20 ➀
200A 240V Ac 200 kAIC 25 60 R, T
Switch 480V Ac 200 kAIC 50 125 R, J, T
600V Ac 200 kAIC 60 150 R, J, T
250V Dc 10 kAIC 40 40 ➀
400A 240V Ac 200 kAIC 50 125 R, T
Switch 480V Ac 200 kAIC 100 250 R, J, T 250 to 750 MCM or
600V Ac 200 kAIC 125 350 R, J, T (2) 3/0 to 250 MCM
250V Dc 10 kAIC 50 50 ➀
600A 240V Ac 200 kAIC 75 200 R, T
Switch 480V Ac 200 kAIC 150 400 R, J, T
600V Ac 200 kAIC 200 500 R, J, T
800A 240V Ac 200 kAIC N/A N/A T
Switch 480V Ac 200 kAIC N/A N/A L, T
600V Ac 200 kAIC N/A N/A L, T
1200A 240V Ac 200 kAIC N/A N/A T
Switch 480V Ac 200 kAIC N/A N/A L
600V Ac 200 kAIC N/A N/A L
22" wide, 15X high
22" wide, 16X high - Bottom Feed Main22" wide, 16X high - Top Feed Main
1200A
Switch Selection Guide
Rating Fuse Catalog Number
240 Volts Ac
1200 T FDPW328F
1200 (Main) T FDPW328MF
600 Volts Ac
1200 L FDPW368
1200 (Main) L FDPW368M
Rating Fuse Catalog Number
240 Volts Ac
1200 T FDPW328TF
600 Volts Ac
1200 L FDPW368T
Rating Fuse Catalog Number
240 Volts Ac
1200 T FDPW328BF
600 Volts Ac
1200 L FDPW368B
For cable-in/cable-out application of a branch
switch, additional terminals are required. Order
4 of the following terminal kit: TA750FDPW
Each kit contains 3 terminals and hardware.
For cable-in/cable-out application of a branch
switch, additional terminals are required. Order
4 of the following terminal kit: TA750FDPW
Each kit contains 3 terminals and hardware.
For cable-in/cable-out application of a branch
switch, additional terminals are required. Order
4 of the following terminal kit: TA750FDPW
Each kit contains 3 terminals and hardware.
➀ Contact fuse manufacturer for UL listed Dc fuses.
N/A Not Applicable
Standard Maximum
#14 to 1/0
#14 to 1/0
#14 to 1/0
#4 to 300 MCM
(2) #4 to 600 MCM or
(4) 3/0 to 250 MCM
(3) 250 to 750 MCM or
(6) 3/0 to 250 MCM
(4) 250 to 750 MCM or
(8) 3/0 to 250 MCM
Time/Current Curves, Dimension Sheets, Application Data