Datasheet

05/23/2017 Eaton Industries GmbH
http://www.eaton.eu
© 05/2017 by Eaton Industries GmbH
278576 - HPL-ED2017 V32.0 EN
2 / 2
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical�data�ETIM�6.0
Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042)
Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) (ecl@ss8.1-27-14-19-01
[AAB905011])
Release characteristic D
Number of poles (total) 1
Number of protected poles 1
Nominal rated current A 4
Nominal rated voltage V 230
Rated short-circuit breaking capacity Icn EN 60898 at 230 V kA 10
Rated short-circuit breaking capacity Icn EN 60898 at 400 V kA 10
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V kA 15
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V kA 15
Voltage type AC
Current limiting class 3
Frequency Hz 50 - 60
Concurrently switching N-neutral No
Suitable for flush-mounted installation No
Over voltage category 3
Pollution degree 2
Width in number of modular spacings 1
Built-in depth mm 70.5
Additional equipment possible Yes
Degree of protection (IP) IP20
Approvals
Product Standards IEC/EN 60947-2; IEC/EN 60898; UL 1077; CSA-C22.2 No. 235; CE marking
UL File No. E177451
UL Category Control No. QVNU2, QVNU8
CSA File No. 204453
CSA Class No. 3215-30
North America Certification UL recognized, CSA certified
Conditions of Acceptability Supplementary Protector only
Suitable for Branch Circuits; not as BCPD
Current Limiting Circuit-Breaker No
Max. Voltage Rating 277 VAC; 48 VDC
Degree of Protection IEC: IP20; UL/CSA Type: -