Datasheet

Specifications are subject to change without notice. Copyright 2011 Eaton Industries Pty Ltd
Technical Specification –ESF series surge filters
Tvss Doc# 510ESF
Page 6 of 6
PHYSICAL AND ELECTRICAL SPECIFICATIONS CONTINUED
Terminations Bolted lug. 8mm bolts for phase and neutral
connections. 6mm PE (earth) stud provided on gear
tray. All connections identified on unit.
Alarms/indicators Includes status indicators, dry contact alarm relay
output (normally-closed with power applied and all
SPD’s at 100% capacity). Contact rating
250Vac/32Vdc, 5A, alarm under-voltage cut off
180Vac.
Location Category Internal mounting location only. Must be installed
within a suitable enclosed space, allowing for
cooling airflow.
Thermal dissipation Max 200W @ full load, 3 phase, 80A model.
Standards. Designed in accordance with : IEC61643-1:2007, IEC610006-1,2,3,4 ANSI/IEEE
C62.41, AS/NZS1768, AS/NZS3000:2007, AS3100
Installation instructions Supplied with unit.
Dimensions – 1 phase including hinges Enclosed models : 520H x 240W x 220D (mm)
Gear tray models : 350H x 200W x 190D
Dimensions – 3 phase including hinges Enclosed models :520H x 400W x 220D (mm)
Gear tray models : 350H x 360W x 190D
Weight 6kg (single phase), 10kg (3 phase)
Environment
-10 to 65°C, 10 to 90%RH (non-condensing)
IP42 Enclosed
IP20 Gear tray
Warranty 5 years, workmanship and materials
NOTE:- Installation must be carried out by suitably qualified personnel. Please refer to installation instructions prior
to proceeding with installation.