Datasheet
DC-13
24 V I
e
A 2
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD)
applied standard IEC EN 61000-4-2, Level 3
Air discharge kV 8
Contact discharge kV 6
Electromagnetic fields (RFI)
applied standard IEC/EN 61000-4-3
V/m 800 - 1000 MHz: 10
1.4 - 2 GHz: 10
2.0 - 2.7 GHz: 3
Radio interference suppression EN 55011, Class A (emitted interference, line-conducted)
EN 61000-6-3, Class A (emitted interference, radiated)
Note on use This product is designed for operation in industrial environments (environment
2). The use in residential environments (environment 1) could cause electrical
interference so that addition suppression must be planned.
Burst kV 2
IEC/EN 61000-4-4, level 3
power pulses (Surge) 1 kV (symmetrical)
2 kV (asymmetrical)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6) V 10
Technical safety parameters:
Notes Safe switch off.
See Safety manual PU05907001Z.
Ambient temperature °C 40
Values according to EN ISO 13849-1
MTTF
d
Years 421
Performance level PL e
Category 3
Values according to IEC 62061
λsd [FIT]: 47
λsu [FIT]: 1582
λdd [FIT]: 269
λdu [FIT]: 2,4
SGF [%]: 99,8
DCS [%]: 2,9
DC [%]: 99
PFH [1/h]: 2,4 x 10
-9
SIL: 3
Notes Safe switch off.
See Safety manual PU05907001Z.
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 2.4
Heat dissipation per pole, current-dependent P
vid
W 0.7
Equipment heat dissipation, current-dependent P
vid
W 2
Static heat dissipation, non-current-dependent P
vs
W 1
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 60
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
12/28/2018 Eaton 170103 ED2018 V51.0 EN 3 / 6