Datasheet

45-8
CA08102001E
Circuit Breakers & Supplementary Protectors
45
15 – 2500 Amperes for UL, CSA & IEC Applications
Frame Sizes EG through RG
Table 45-3. EG through RG Electrical Characteristics (Continued)
Technical Data EG JG LG NG RG
Conductor Cross Sections and Terminal Types
for Main Conductors
Solid or Stranded
Finely Stranded with End Sleeve
Bus Bar
Tightening Torque for Box Terminals
Tightening Torque for Bus Bar Connection Pieces
Box Terminals
2.5 to 95 mm
2
2.5 to 50/70 mm
2
5.6 Nm
5.6 Nm
Box Terminals
50 to 150 mm
2
35 to 120 mm
2
20 Nm
15 Nm
Box Terminals
95 to 240 mm
2
70 to 150 mm
2
42 Nm
30 Nm
Flat Bar
Terminals
600 A
31 Nm
6 Nm
Flat Bar Terminals
Optional
31 Nm
50 Nm
Flat Bar Terminals
Optional
20 Nm
Conductor Cross Sections for Auxiliary Circuits
with Terminal Connection or Terminal Strip
Solid
Finely Stranded with End Sleeve
With Brought-out Cable Ends
Tightening Torque for Fitting Screws
0.75 to 2.5 mm
2
0.75 to 2.5 mm
2
0.75 to 2.5 mm
2
0.75 to 2.5 mm
2
0.82 (AWG 18) mm
2
0.8 to 1.4 Nm
0.75 to 2.5 mm
2
0.75 to 2.5 mm
2
0.82 (AWG 18) mm
2
0.8 to 1.4 Nm
Up to 2x4 mm
2
Up to 2x2.5 mm
2
0.82 (AWG 18) mm
2
0.8 to 1.4 Nm
Up to 2x4 mm
2
Up to 2x2.5 mm
2
0.82 (AWG 18) mm
2
0.8 to 1.4 Nm
Power Loss per Circuit Breaker at Maximum
Rated Current l
n
(The Power Losses of the
Undervoltage Releases (“r” Releases) Must Be
Observed if Necessary) at Three-Phase
Symmetrical Load)
For Plant Protection
As Isolating Circuit Breaker
For Starter Combinations
For Motor Protection
40 W
40 W
40 W
45 W
45 W
45 W
45 W
400 A:
65 W
65 W
65 W
65 W
600 A:
120 W
120 W
120 W
120 W
87/210 W
87/210 W
220/270/400 W
220/270/400 W
Permissible Mounting Position
Arc Spacing —
Suitable for Reverse-Feed Applications
Yes
(Except HMCPE)
Yes Yes Yes Yes
90°
90°
90°
90°