Cut Sheet
V10-T15-38 Volume 10—Enclosed Control CA08100012E—June 2015 www.eaton.com
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15.1
Accessories and Modification Codes
Accessories
Heater Coils
Heater Coil Selection for Type B Overload Relay
Notes
1
Three are required per overload relay.
For information on H2001 heaters, see Page V10-T15-6.
Motor Full Load Current in Amperes for Use with 3 Heaters Only Motor Full Load Current in Amperes for Use with 3 Heaters Only
Open Starter
Heater
Catalog Number
1
Open Starter
Heater
Catalog Number
1
Ambient Compensated
Overload Relay
Ambient Compensated
Overload Relay
Size 4 and 160A Size 5 and 320A with 300/5 Current Transformers
12.8–14.1 FH68 107–117 FH23
14.2–15.5 FH69 118–129 FH24
15.6–17.1 FH70 130–141 FH25
17.2–18.9 FH71 142–155 FH26
19.0–20.8 FH72 156–170 FH27
20.9–22.9 FH73 171–187 FH28
23.0–25.2 FH74 188–205 FH29
25.3–27.8 FH75 206–224 FH30
27.9–30.6 FH76 225–244 FH31
30.7–33.5 FH77 245–263 FH32
33.6–37.5 FH78 264–292 FH33
37.6–41.5 FH79 293–318 FH34
41.6–46.3 FH80 319–350 FH35
46.4–50 FH81 Size 6 and 540A with 600/5 Current Transformers
51–55 FH82 236–259 FH24
56–61 FH83 260–283 FH25
62–66 FH84 284–310 FH26
67–73 FH85 311–340 FH27
74–78 FH86 341–374 FH28
79–84 FH87 375–411 FH29
85–92 FH88 412–448 FH30
93–101 FH89 449–489 FH31
102–110 FH90 490–527 FH32
111–122 FH91 528–585 FH33
123–129 FH92 586–600 FH34
1
30–133 FH9
3
— FH94