Cut Sheet

Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com V10-T6-19
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6.3
Pump Panels
Irrigation Pump Panels
Pump Panels—Interchangeable Heater Overload
Product Selection
Standard ECP54 controllers
have a HAND/OFF/AUTO
selector switch and START
pushbutton mounted on the
enclosure and are wired as
illustrated on Page V10-T6-22.
Class ECP54—Combination Irrigation Pump Panel—Fusible Disconnect
Fuse Clips
C351—Fuse Clip Selection—Three-Pole (Three Fuses)
Notes
Starters do not include heater packs. Select one carton of three heater packs. For heater pack selection, see Tab 15.
1
Dual element fuse ratings.
2
Class R fuse clips.
3
For Compact NEMA Size 1 or Size 4 Pump Panel, add modification code C60. (Example: ECN5412AAA-C60).
4
Fuse clip “R” rejection members for use with Class R fuses are supplied loose both in fuse clip kits and when fuse clips are factory installed.
NEMA
Size
Motor
Voltage
1
Max. hp
50/60 Hz
Fuse Clip Rating
2
Standard Width
Amperes Volts Catalog Number
1
3
230 7-1/2 30 250 ECP5412BAB
460 10 600 ECP5412CAC
Not installed Not installed ECP5412AAA
2 230 15 60 250 ECP5422BAD
460 25 600 ECP5422CAE
Not installed Not installed ECP5422AAA
3 230 30 100 250 ECP5432BAF
460 50 600 ECP5432CAG
Not installed Not installed ECP5432AAA
NEMA
Size
Motor
Voltage
Fuse Clip Rating
Fuse Clip Kit for Field Installation in
Non-Fusible Starter
For Non-Rejection
Type Fuses
For Use with “R”
Rejection Type Fuses
Amperes Volts Catalog Number Catalog Number
1 200/230 30 250 C351KC21 C351KC21R
460–575 600 C351KD22-61 C351KD22-61R
2 200 60 250 C351KD22-61 C351KD22-61R
230 C351KD22-61 C351KD22-61R
460–575 C351KD62 C351KD62R
3 200 100 250 C351KE23-63 C351KE23-63
4
230 C351KE23-63 C351KE23-63
4
460–575 600 C351KE23-63 C351KE23-63
4
Compact NEMA Size 1 and Size 4 Starters
Electrical Life at Rated Continuous Current
NEMA
Size
Rated Current (Amp)
AC3/AC4 Operations
1C 27/150 2,500,000/40,000
1 27/153 5,000,000/110,000
For Other Volts and Hertz
Applications
For other than listed volts and
hertz, select required
controller by catalog number
and replace the magnet coil
alpha designation, eighth digit
in catalog number with proper
code suffix from the table
below.
Example: For 600V 60 Hz coil,
change ECP5412BAB to
ECP5412DAB.
Coil Voltage
Coil Volts and Hertz Suffix Code
120/60 or 110/50 A
240/60 or 220/50 B
480/60 or 440/50 C
600/60 or 550/50 D
208/60 E