User Manual

Commissioning
78
08/04 AWB2528-1423GB
Configuring an easy-NET
network
If you want to work with the easy-NET network and
communicate with several stations, the network must be
configured first.
Proceed as follows:
X Connect all network stations. easy-NET socket 2e to
easy-NET socket 1L.
X The first station 1 (socket 1L) and the last station
(socket 2e) must be provided with a network termination
resistor a.
X Connect all stations to the power supply.
Figure 49: Example topology with two easy-NET stations
a Network termination resistor
Physical location
Station number
X Switch on the power supply on all stations.
X Ensure that all stations have a voltage supply. The POW
LED must light up or flash. It is only possible to configure
the stations which are supplied with voltage.
X Proceed to the first physical station (Location 1). This
station has the termination resistor inserted in socket 1.
1
1
I1 – I12
Q1 – Q8
2
2
I1 – I12
Q1 – Q6
R1 – R12
S1 – S8
a
a
h
The following tasks are only possible in STOP mode.