User Manual
Commissioning
66
08/04 AWB2528-1423GB
X Press OK to confirm your choice and press ESC to exit the
menu.
easy will then switch to the Status display.
easy operating modes easyeasy has two operating modes - RUN and STOP.
In RUN mode easy continuously processes a stored circuit
diagram until you select STOP or disconnect the power. The
circuit diagram, parameters and the easy settings are
retained in the event of a power failure. All you will have to
do is reset the real-time clock after the back-up time has
elapsed.Circuit diagram entry is only possible in STOP mode.
The following applies to devices without display/operating
unit:
• Memory card containing a valid circuit diagram is fitted.
• Device is switched on.
If the device does not contain a circuit diagram, the circuit
diagram on the memory card is loaded automatically and
the device processes the circuit diagram immediately in RUN
mode.
h
You can change the language setting at a later date, if you
wish, see a Section “Changing the menu language”,
Page 270.
If you do not set the language, easy will display this menu
every time you switch on and wait for you to select a
language.
Caution!
In RUN mode, easy will immediately run the program
saved in the unit when the power supply is switched on.
This will not happen if STOP mode was set as startup
mode. In RUN mode outputs are activated according to
the switch logic involved.