User Manual

Connecting the NET network
57
08/04 AWB2528-1423GB
Connection cable:
4-pair twisted cable; a chapter “Technical data”,
Page 330
Figure 35: Connection assignment
ECAN_H data cable, pin 1, cable pair A
ECAN_L data cable, pin 2, cable pair A
Ground cable GND, pin 3, cable pair B
Select cable SEL_IN, pin 4, cable pair B
Table 3: Prefabricated cables, RJ45 plug on both ends
Material for self-manufactured cables
100 m 4 x 0.18 mm
2
: EASY-NT-CAB
Required crimping tool for RJ45 plug: EASY-RJ45-TOOL
Bus termination resistor
The first and last stations in the network must be provided
with a bus termination resistor.
Value: 124 O
Termination connector: EASY-NT-R
A1ECAN_H
A2ECAN_L
B 3 GND (Ground)
B 4 SEL_IN
h
Minimum operation with easy-NET functions with the
cables ECAN_H, ECAN_L and GND. The SEL_IN cable is
only used for automatic addressing.
Cable length Type designation
cm
30 EASY-NT-30
80 EASY-NT-80
150 EASY-NT-150