and thus in the interference of analog signals. In this case,
only ground the cable at one end.
X Do not lay signal lines parallel to power cables.
X Connect inductive loads to be switched via the easy
outputs to a separate power feed, or use a suppressor
circuit for motors and valves. If loads such as motors,
solenoid valves or contactors are operated with easy via
the same power feed, switching may give rise to
interference on the analog input signals.
The following circuits contain examples of applications for
analog value processing.
Setpoint potentiometer
Figure 19: Setpoint potentiometer
Use a potentiometer with a resistance of F 1kO, e.g.
1kO,0.25W.
h
Ensure that the reference potential is connected. Connect
the 0 V of the power supply unit for the different setpoint
potentiometers and sensors shown in the examples to the
0 V terminal of the easy power feed.