User Manual

Connecting the inputs
39
08/04 AWB2528-1423GB
Cable protection
Both easy AC and DC versions require cable protection (F1)
rated for at least 1 A (slow).
Connecting the inputs easy inputs switch electronically. Once you have connected
a contact via an input terminal, you can reuse it as a contact
in your easy circuit diagram as often as you like.
Figure 10: Connecting the inputs
Connect contacts such as push-button actuators or switches
to easy input terminals.
Connecting the AC inputs
h
When easy is switched on for the first time, its power
supply circuit behaves like a capacitor. Use an appropriate
device for switching on the power supply and do not use
any reed relay contacts or proximity switches.
+24 V
S1
0 V
I1
I1 i1
L
N
Caution!
For easy-AC, connect the inputs to the same line as the
power feed in accordance with the VDE, IEC, UL and CSA
safety regulations. Otherwise easy will not detect the
switching level and may be damaged or destroyed by
overvoltage.