User Manual
Terminals
35
08/04 AWB2528-1423GB
Terminals Tools
Slot-head screwdriver, width 3.5 mm, tightening torque
0.6 Nm.
Cable cross-sections
• Solid: 0.2 to 4 mm
2
(AWG 22 - -12)
• Flexible with ferrule: 0.2 to 2.5 mm
2
(AWG 22 -12)
Network cables and plug Use the prefabricated EASY-NT-“Length” cables when
possible.
Other cable lengths can be manufactured using the
EASY-NT-CAB cable, the EASY-NT-RJ45 plug as well as the
EASY-RJ45-TOOL crimping tool.
AWG 24, 0.2 mm
2
are the largest crimpable cross-sections.
The first and last stations in the network must each be
terminated with the EASY-NT-R bus termination resistor.
Connecting the power
supply
h
For the connection data of both versions, easy-DC with
24 V DC and easy-AC with standard voltages of 100 V to
240 V AC, refer to Chapter “Technical data” from
Page 318.
The easy800 devices run a system test for one second after
the power supply has been switched on. Either RUN or
STOP mode will be activated after this time depending on
the default setting.