User Manual

Technical data
329
08/04 AWB2528-1423GB
Other inductive loads:
Analog output
EASY8..-D.-T..
T
0.95
= 15 ms
R = 48 O
L = 0.24 H
Utilisation factor g = 0,25
Relative duty factor % 100
Max. switching frequency
f = 0.5 Hz
Max. duty factor
DF = 50 %
Switch
operations/h
1500
Inductive loading with external suppressor circuit for each load
(a Section “Connecting transistor outputs”, Page 53)
Utilisation factor g = 1
Relative duty factor % 100
Max. switching frequency
Max. duty factor
Switch
operations/h
Depends on the
suppressor
circuit
EASY8..-DC-T..
Number 1
Electrical isolation
To power supply No
To the digital inputs No
To the digital outputs Yes
To the easy-NET network Yes
Output type: DC voltage
Signal range V DC 0 to 10
Output current max. mA 10
Load resistor k O 1
Short-circuit and overload proof Yes