User Manual

Technical data
327
08/04 AWB2528-1423GB
Lamp load
Q1 to Q4 without R
V
W 3
Q5 to Q8 without R
V
W 5
Residual current at state “0” per channel mA < 0.1
Max. output voltage
On 0 state with external load, 10 MO V 2,5
On 1 state, I
e
= 0.5 A U = U
e
– 1 V
Short-circuit protection
Thermal (Q1 to Q4)
(evaluation with diagnostics inputs I16, I15)
Yes
Short-circuit tripping current for R
a
F 10 mO
(depending on number of active channels and their
load)
A 0.7 F I
e
F 2
Maximum total short-circuit current A
8
Peak short-circuit current A
16
Thermal cutout Yes
Maximum switching frequency with constant resistive
load R
L
= 100 kO (depends on program and load)
Switch
operations/
h
40000
Parallel connection of outputs with resistive load; inductive load with
external suppression circuit (a Section “Connecting transistor outputs”,
Page 53); combination within a group
Yes
Group 1: Q1 to Q4
Group 2: Q5 to Q8
Maximum number of outputs 4
Total maximum current
Attention!
Outputs must be actuated simultaneously and for the
same time duration.
A
2
Status display of the outputs
LCD display (if
provided)
EASY8..-DC-T..