User Manual

Appendix
324
08/04 AWB2528-1423GB
Relay outputs
EASY8..-..-R..
EASY8..-..-R..
Number 6
Type of outputs Relays
In groups of 1
Connection of outputs in parallel to increase the output Not permissible
Protection for an output relay
Miniature circuit-breaker B16 A 16
or fuse (slow-blow) A
8
Potential isolation to mains power supply, input, PC interface, memory
card, NET network, EASY-LINK
Yes
Safe isolation V AC
300
Basic insulation V AC 600
Mechanical lifespan Switch
operations
10 x 10
6
Contacts relays
Conventional thermal current, (UL) A 8, (10)
Recommended for load at 12 V AC/DC mA > 500
Protected against short-circuit cos v = 1
16 A characteristic B (B16) at
A
600
Protected against short-circuit cos v = 0.5 to 0.7
16 A characteristic B (B16) at
A
900
Rated impulse withstand voltage U
imp
contact coil kV 6
Rated insulation voltage U
i
Rated operational voltage U
e
V AC 250
Safe isolation to EN 50178 between coil and contact V AC 300
Safe isolation to EN 50178 between two contacts V AC 300