User Manual

Appendix
316
08/04 AWB2528-1423GB
Burst (IEC/EN 61000-4-4, severity level 3)
Power cables kV 2
Signal cables kV 2
High energy pulses (Surge) easy-AC
(IEC/EN 61000-4-5), power cable symmetrical
kV 2
High energy pulses (Surge) easy-DC
(IEC/EN 61000-4-5, severity level 2), power cable
symmetrical
kV 0,5
Line-conducted interference (IEC/EN 61000-4-6) V
10
Dielectric strength
Measurement of the air clearance and creepage distance EN 50 178, UL 508, CSA
C22.2, No 142
Dielectric strength EN 50 178
Overvoltage category/degree of pollution II/2
Tools and cable cross-sections
Solid, minimum to maximum mm
2
0.2 to 4
AWG 22 to 12
Flexible with ferrule, minimum to maximum mm
2
0.2 to 2.5
AWG
22 to 12
Factory wiring: AWG 30
Slot-head screwdriver, width mm 3.5 x 0.8
inch 0.14 x 0.03
Tightening torque Nm 0,6