User Manual

easy Settings
286
08/04 AWB2528-1423GB
Transferring retentive behaviour
The setting for retentive behaviour is a circuit diagram
setting. In other words, the setting of the retentive menu
may also under certain circumstances be transferred to the
memory card or by uploading or downloading from the PC.
Changing the operating mode or the circuit diagram
When the operating mode is changed or the easy circuit
diagram is modified, the retentive data is normally saved
together with their actual values. The actual values of relays
no longer being used are also retained.
Changing the operating mode
If you change from RUN to STOP and then back to RUN, the
actual values of the retentive data will be retained.
Modifying theeasy circuit diagram
If a modification is made to the easy circuit diagram, the
actual values will be retained.
Changing the startup behaviour in the SYSTEM menu
The retentive actual values are retained in easy regardless of
the setting.
Modification of the retentive range
If the set retentive ranges are reduced, only the actual values
saved in the range will remain.
If the retentive range is extended, the older data is retained.
The new data is written with the current actual values in
RUN mode.