User Manual

easy-NET network
260
08/04 AWB2528-1423GB
Evaluation occurs at the following intervals:
If the absence of a “sign of life” is detected, the respective
diagnostics contact is set to the 1 state.
Baud rate Stations must send a “
sign of life” every ...
Stations recognise the
absence of a "sign of
life" signal after
[KB]
[ms] [ms]
1000 60 180
500
60 180
250 120 360
125 240 720
50 600 1800
20 1500 4500
10 3000 9000
Diagnostics
contact
Station
number
ID 01 1
ID 02 2
ID 03 3
ID 04
4
ID 05 5
ID 06 6
ID 07 7
ID 08 8
h
If a station does not send a “sign of life” signal (station
not available, NET interrupted), the respective diagnostics
contact ID .. is activated.