User Manual

Configuration of the easy-NET
network
253
08/04 AWB2528-1423GB
Configuration of the
easy-NET network
easy-NET can be configured so that it can be optimised for
your application.
Station number
The station number is identified as the NET-ID: in the device.
The station number can be set on devices with a display
using the buttons on the easy800.
Valid station numbers for operation are 01 to 08.
Station number 00 = factory default setting
With station number 00, double address assignment cannot
occur when an existing device is being exchanged.
Transmission speed
The easy800 device hardware allows you set transmission
speeds between 10 and 1000 KBaud in specific stages. In
doing so, the length of all cables is linked to the maximum
data transfer rate (a chapter “Technical data”, Page 330).
The data transfer rate is set under the BAUDRATE: menu
item.
Possible baud rates are: 10, 20, 50, 125, 250, 500 and
1000 KB
125 KB = factory default setting
h
All the easy-NET settings are best carried out on station 1.
The entire network can be configured via station 1. The
configuration should only be carried out locally when a
device is replaced.