User Manual

Function blocks
227
08/04 AWB2528-1423GB
Inputs
The function block input
>I1 can be assigned the following
operands:
•Constants
Markers MD, MW, MB
Analog inputs IA01 to IA04
IA01: terminal I7
IA02: terminal I8
IA03: terminal I11
IA04: terminal I12
Analog output QA01
Actual value
QV> of another function block
Displaying the parameter set in the PARAMETERS
menu
+ Access enabled
– Access disabled
Coils
ST01EN, enable coil.
Memory requirement of the function block
The set cycle time function block requires 24 bytes of
memory plus 4 bytes per constant on the function block
input.
Function of the set cycle time function block
The function block is used to define a fixed cycle time.
Actual cycle time is less than the set cycle time:
If the maximum cycle time present is less than the set cycle
time, the set cycle time is constant.
Actual cycle time is greater than the set cycle time:
If the maximum cycle time present is greater than the set
cycle time, the set cycle time has no effect.
h
The function block must be enabled so that it can work.
Coil ST01EN is active. If coil ST01EN is not active, the
entire function block is deactivated and reset.