User Manual
Wiring with easy800
222
08/04 AWB2528-1423GB
Figure 101: easy800 circuit diagram with pulse width modulation.
Parameter display and parameter set for pulse width
modulation:
The parameter display for a timing relay is used to modify the
period duration, the minimum on time and the enabling of
the parameter display.
Value and time ranges
Inputs
The function block inputs
>SV, >PD and >ME can be
assigned the following operands:
•Constants
• Markers MD, MW, MB
h
To prevent unpredictable switching states, use each coil of
a relay once only in the circuit diagram.
M 95---------------------------Ä PW01EN
PW01E1-------------------------Ä M 96
PW02 +
>SV
>PD
>ME
PW02 Pulse width modulation function block number 02
+ Appears in the parameter display
>SV Manipulated variable input
>PD Period duration in ms
>ME Minimum on duration, minimum off duration in ms
Parameter Value and time range Resolution
SV 0 to 4095 1 digit
PD 0 to 65535 ms
ME 0 to 65535 ms
h
The minimum time setting for the period duration is:
0.005 s (5 ms)