Example 6
Overlapping ranges
Total number of channels and behaviour of the contact
HY01Q1:
The time switch will switch on at 00:00 from the 3rd May
and off at 23:59 on the 25th May.
In June, July, August, September, October, the time switch
will switch on at 00:00 on the 2nd of the month and switch
off at 23:59 on the 17th.
In November and December, the time switch will switch on
at 00:00 on the 2nd of the month and switch off at 23:59 on
the 17th.
Value scaling
This function block is available from device version 04.
easy provides 32 value scaling function blocks LS01 to LS32.
The function block enables you to convert values from one
value range to another one. In this way it is possible to
reduce or increase values.
Wiring of a scaling function block
You can integrate a value scaling function block into your
circuit as a coil.
Figure 93: easy800 circuit diagram with LS value scaling
The year time switch HY01
channel A switches on at
00:00 on the 3rd of the
months 5, 6, 7, 8, 9, 10 and
remains on until 23:59 on the
25th of these months.
The year time switch HY01
channel B switches on at
00:00& on the 2nd in the
months 6, 7, 8, 9, 10, 11, 12
and remains on until 23:59 on
17th of these months.
HY01 A +
>ON 03.05.--
>OFF 25.10.--
HY01 B +
>ON 02.06.--
>OFF 17.12.--
M 48----------------------------Ä LS27EN