User Manual
Wiring with easy800
196
08/04 AWB2528-1423GB
Wiring of a 7-day time switch
A 7-day time switch is integrated into the circuit diagram as
a contact.
Figure 88: easy800 circuit diagram with 7-day time switch
Parameter display and parameter set for the 7-day time
switch HW:
Channels
4 channels are available per time switch, channels A, B, C
and D. These channels all act on the contact of the 7-day
time switch.
Day 1 and day 2
Either the time period acts from day 1 to day 2, e.g. Monday
to Friday, or for one day only.
Monday = MO, Tuesday = TU, Wednesday = WE, Thursday
= TH, Friday = FR, Saturday = SA, Sunday = SU,
Time
00:00 to 23:59
Displaying the parameter set in the PARAMETERS
menu
• + Access enabled
• – Access disabled
HW14Q1---------------------------Ä Q 01
HW14 A +
>DY1
>DY2
>ON
>OFF
HW14 7-day time switch function block number 14
A Time switch channel A
+ Appears in the parameter display
>DY1 Day 1
>DY2 Day 2
>ON On time
>OF
F
Off time