User Manual

Wiring with easy800
186
08/04 AWB2528-1423GB
Value range for inputs and outputs
Example:
Displaying the parameter set in the PARAMETERS
menu
+ Access enabled
– Access disabled
Contacts
DC01LI to DC32LI, value range of the manipulated variable
exceeded.
Coils
DC01EN to DC32EN: Enable PID controller;
DC01EP to DC32EP: Activate proportional component;
DC01EI to DC32EI: Activate integral component;
Value range Resolution/Unit
>I1 Setpoint of PID controller –32 768 to +32767
>I2 Actual value of PID
controller,
–32 768 to +32767
>KP Proportional gain K
p
0 to 65535 in -- /%
>TN Reset time T
n
0 to 65535 in 100/ms
>TV Rate time T
v
0 to 65535 in 100/ms
>TC Scan time 0 to 65535 in 100/ms
>MV Manual manipulated variable –4096 to +4095
QV> Manipulated variable 0 to 4095 (unipolar)
–4096 to +4095 (bipolar)
Value at input Value processed in
the function block.
>KP Proportional gain K
p
1500 15
>TN Reset time T
n
250 25 s
>TV Rate time T
v
200 20 s
>TC
Scan time 500 50 s
>MV Manual manipulated variable 500 500