User Manual
Wiring with easy800
178
08/04 AWB2528-1423GB
Displaying a variable
Actual values of function blocks, markers (MB, MW and
MD), as well as analog inputs (scalable) can be displayed.
The display of date and time is also possible.
Entering setpoint values
This function is available from device version 04.
Function block setpoints, and marker values (MB, MW, MD)
that are constants can be modified via the text function
block.
The variables and setpoints can be inserted at any desired
position in the text. The variables and setpoints can be 4, 7
and 11 places long.
Pay attention to the maximum character length of the
variables setpoints. Otherwise, characters will be
overwritten or not displayed.
Scaling
The values of the analog inputs and analog output can be
scaled.
Function
Text display function block, D = Display: the text display in
the circuit diagram functions as a normal M marker. If a text
is stored in a marker, this is displayed in the easy display
when the coil is set to 1. To use this function, the easy must
be in RUN mode and the Status display must be activated
before the text is displayed.
Range Selectable display
range
Example
0 to 10 V 0 to 9999 0000 to 0100
0 to 10 V g 999 –025 to 050
0 to 10 V g 9.9 –5.0 to 5.0