Function blocks
165
08/04 AWB2528-1423GB
Figure 75: easy800 circuit diagram with high-speed counter
Parameter display and parameter set for high-speed
counters:
In the parameter display of a counter relay you change
setpoint values and/or the preset value and enable of the
parameter display.
Value range
The function block operates in the integer range from
–2147483648 to 2147483647.
Behaviour when value range is exceeded
The function block sets the switching contact CH..CY to
status 1.
The function block retains the value of the last valid
operation.
I 05---------------------------Ä CH01EN
I 06---------------------------Ä CH01RE
I 07---------------------------Ä CH01D_
I 08---------------------------Ä CH01SE
CH01OF-------------------------Ä Q 01
CH01FB-------------------------Ä Q 02
CH01ZE-------------------------Ä Q 03
CH01CY-------------------------S M 94
CH01 +
>SH
>SL
>SV
QV>
CH01 High-speed counter function block number 01
+ Appears in the parameter display
>SH Upper setpoint
>SL Lower setpoint
>SV Defined actual value (Preset)
QV> Actual value in RUN mode
h
Counter CH counts every rising edge on the counter input.
If the value range is exceeded, the switching contact
CH ..CY switches to status 1 for one cycle per rising edge
detected.