User Manual

Wiring with easy800
162
08/04 AWB2528-1423GB
•Constants
Markers MD, MW, MB
Analog inputs IA01 to IA04
IA01: terminal I7
IA02: terminal I8
IA03: terminal I11
IA04: terminal I12
Analog output QA01
Actual value
QV> of another function block
Actual value
QV>
The actual value
QV> can be assigned the following
operands:
Markers MD, MW, MB
Analog output QA01
Displaying the parameter set in the PARAMETERS
menu
+ Access enabled
– Access disabled
Contacts
CF01OF to CF04OF: Actual value f Upper setpoint
CF01FB to CF04FB: Actual value F Lower setpoint
CF01ZE to CF04ZE: Actual value = Zero
Coils
CF01EN to CF04EN: enable of the counter with coil
status = 1.
Memory requirement of the frequency counter
The frequency counter function block requires 40 bytes of
memory plus 4 bytes per constant on the function block
inputs.
Retention
The frequency counter does not retain actual values, as the
frequency is remeasured continuously.