User Manual
Wiring with easy800
112
08/04 AWB2528-1423GB
The Status menu display shows whether the P buttons are
used in the circuit diagram.
Displayed on the Status display:
• P: button function wired and active
• P2: button function wired, active and P2 button
Í pressed
• P-: button function wired and not active
• Empty field: P buttons not used
Checking the circuit diagram
easy800 contains a built-in measuring device enabling you
to monitor the switching states of contacts, relays and
function block coils during operation.
X Create the small parallel circuit below and save it.
Figure 56: Parallel circuit
X Switch easy800 to RUN mode via the main menu.
X Return to the circuit diagram display.
You are now unable to edit the circuit diagram.
The circuit diagram display performs two functions
depending on the mode:
• STOP: Creation of the circuit diagram
• RUN: Power flow display
X Switch on I3.
I123456789…
P2
MO 14:55
Q.2
…6.8 RUN
I 02--u------------------------S Q 01
I 03--k
h
If you switch to the circuit diagram display and are unable
to modify a circuit diagram, first check whether easy800 is
in STOP mode.