User Manual
Wiring with easy800
100
08/04 AWB2528-1423GB
Circuit diagram display
In the easy800 circuit diagram, contacts and coils of relays
are connected up from left to right - from the contact to the
coil. The circuit diagram is created on a hidden wiring grid
containing contact fields, coil fields and circuit connections.
It is then wired up with connections.
• Insert contacts in the four contact fields. The first
contact field on the left is automatically connected to the
voltage.
• Insert the relay coil to be controlled together with its
function and designation in the coil field. The coil
designation consists of the coil name, coil number and
function block from the function designation. The coil
function defines the method of operation of the coil.
• Every line in the circuit diagram forms a rung. With the
easy800 up to 256 circuit connections can be wired in a
circuit diagram
I 01----I 02----CP01GT---------Ä Q 01
Q 01----HY01Q1k''''''' ''''''' ''''''''
''''''' ''''''' ''''''' ''''''' ''''''''
L: 1 C:1 B:____
Contact fields (1 to 4) Coil field (5)
Circuit
Circuit
Status line
Number of the
circuit
Number of
the field in the
circuit
Amount of free
memory in bytes