Datasheet

500 W at 115/120 V AC Operations 25000
Fluorescent lamp load
Fluorescent lamp load 10 x 58 W at 230/240 V AC
With upstream electrical device Operations 25000
Uncompensated Operations 25000
Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated Operations 25000
Switching frequency
Mechanical operations
x 10
6
10
Switching frequency Hz 10
Resistive load/lamp load Hz 2
Inductive load Hz 0.5
UL/CSA
Uninterrupted current at 240 V AC A 10
Uninterrupted current at 24 V DC A 8
AC
Control Circuit Rating Codes (utilization category) B 300 Light Pilot Duty
Max. rated operational voltage V AC 300
max. thermal continuous current cos ϕ = 1 at B 300 A 5
max. make/break cos ϕ ≠ capacity 1 at B 300 VA 3600/360
DC
Control Circuit Rating Codes (utilization category) R 300 Light Pilot Duty
Max. rated operational voltage V DC 300
Max. thermal uninterrupted current at R 300 A 1
Max. make/break capacity at R 300 VA 28/28
Ethernet
Data transfer rate Mbit/s 10/100
Connections RJ45 plug, 8-pin
Cable CAT5
Design verification as per IEC/EN 61439
Technical data for design verification
Static heat dissipation, non-current-dependent P
vs
W 3
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Meets the product standard's requirements.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.