Datasheet

Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Vibrations Hz In accordance with IEC 60068-2-6
constant amplitude 0.15 mm: 10 - 57
constant acceleration 2 g: 57 - 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms Impacts 18
Drop to IEC/EN 60068-2-31 Drop height mm 50
Free fall, packaged (IEC/EN 60068-2-32) m 0.3
Mounting position Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree III/2
Electrostatic discharge (ESD)
applied standard according to IEC EN 61000-4-2
Air discharge kV 8
Contact discharge kV 6
Electromagnetic fields (RFI) to IEC EN 61000-4-3 V/m 0.8 - 1.0 GHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1
Radio interference suppression EN 61000-6-3 Class B
Burst kV according to IEC/EN 61000-4-4
Supply cables: 2
Signal cables: 2
power pulses (Surge) according to IEC/EN 61000-4-5
0.5 kV (supply cables, symmetrical)
1 kV (supply cables, asymmetrical)
Immunity to line-conducted interference to (IEC/EN 61000-4-6) V 10
Insulation resistance
Clearance in air and creepage distances nach EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Insulation resistance in accordance with EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO.
61010-2-201
Power supply
Rated operational voltage U
e
V 24 DC (-15/+20%)
Permissible range U
e
20.4 - 28.8 V DC
Residual ripple % ≦ 5
Siemens MPI, (optional) yes
Input current max. 40 mA at Ue
Voltage dips ms ≤ 10
Fuse A ≧ 2.5A (T)
Heat dissipation at 24 V DC W 1
Digital inputs 24 V DC
Number 4
Potential isolation from power supply: no
between inputs: no
from the outputs: no
to expansion devices: yes
to base unit: yes
Rated operational voltage U
e
V DC 24
Input voltage V DC Signal 0: ≦ 5 (I1 - I4)
Signal 1: ≧ 15 (I1 - I4)
Input current at signal 1 mA 3.3 (I1 – I4)
Deceleration time ms type 0.1 (0 -> 1)
type 0.2 (1 -> 0)
Cable length m 100 (unshielded)
Transistor outputs
Number 4
Rated operational voltage U
e
V DC 24
Permissible range U
e
20.4 - 28.8 V DC
Residual ripple % 5
Siemens MPI, (optional) Yes (Caution: A short circuit will occur if a supply voltage of the wrong polarity is
applied to the outputs.)
Potential isolation from power supply: no
between the inputs: no
to the outputs: no
to base unit: yes
to expansion devices: yes
06/13/2019 Eaton Y7-197219 ED2019 V57.0 EN 2 / 6