Data Sheet

Transistor outputs
Number 8
Rated operational voltage U
e
V DC 24
Permissible range U
e
20.4 - 28.8 V DC
Residual ripple % 5
Protection against polarity reversal Yes (Caution: A short circuit will occur if a supply voltage of the wrong polarity is
applied to the outputs.)
Potential isolation from power supply: no
between the inputs: no
to the outputs: no
to base unit: yes
to expansion devices: yes
Rated operational current at signal „1” DC per channel I
e
A Max. 0.5
Residual current on 0 signal per channel mA < 0.005
Max. output voltage V 1 (at status 0 per channel)
U = U
e
- 1 V (signal 1 at I
e
= 0.5 A)
Short-circuit protection yes, electronic (Q1 - Q4, Q5 - Q8)
Short-circuit tripping current for R
a
≦ 10 mΩ A 0.7 ≦ I
e
≦ 1.7 per output
depending on number of active channels and their load
Total short-circuit current A 13.6
Thermal cutout Yes
Max. operating frequency with constant resistive load Operations/
h
abhängig von der Zykluszeit des Basisgeräts und bei Erweiterungsgeräten auch
von deren Übertragungszeit
Parallel connection of outputs
With resistive load, inductive load with external suppressor circuit,
combination within a group
Group 1 Q1 to Q4
Group 2 Q5 to Q8
Number of outputs max. 8
Max. total current A 4
Inductive load to EN 60947-5-1
Without external suppressor circuit
DC-13, T
0.95 = 72 ms, R = 48 Ω, L = 1.15 H
Utilization factor g 0.25
Duty factor % DF 100
T
0.95 = 15 ms, R = 48 Ω, L = 0.24 H
Utilization factor g 0.25
Duty factor % DF 100
With external suppressor circuit
Utilization factor g 1
Duty factor % DF 100
Max. switching frequency, max. duty factor OperationsDepending on the suppressor circuit
Design verification as per IEC/EN 61439
Technical data for design verification
Static heat dissipation, non-current-dependent P
vs
W 1
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Meets the product standard's requirements.
10.4 Clearances and creepage distances Meets the product standard's requirements.
06/18/2021 Eaton Y7-197220 ED2021 V80.0 EN 3 / 6