Datasheet
480 V
575 V
600 V
HP 5
Single-phase
115 V
120 V
HP 0.25
230 V
240 V
HP 1
General use A 20
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 1
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 5
max. Fuse A 45
max. CB A 60
480 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 25 Class RK5/20 Class J
SCCR (CB) kA 65
max. CB A 16
600 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 25 Class RK5/20 Class J
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3phase, 277V 60Hz 1phase A 12
600V 60Hz 3phase, 347V 60Hz 1phase A 12
Incandescent Lamps (Tungsten)
480V 60Hz 3phase, 277V 60Hz 1phase A 14
600V 60Hz 3phase, 347V 60Hz 1phase A 14
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase A 12
600V 60Hz 3phase, 347V 60Hz 1phase A 12
Refrigeration Control (CSA only)
LRA 480V 60Hz 3phase A 60
FLA 480V 60Hz 3phase A 10
LRA 600V 60Hz 3phase A 60
FLA 600V 60Hz 3phase A 10
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
LRA 480V 60Hz 3phase A 42
FLA 480V 60Hz 3phase A 7
Elevator Control
200V 60Hz 3phase HP 0.75
200V 60Hz 3phase A 3.7
240V 60Hz 3phase HP 1.5
240V 60Hz 3phase A 6
480V 60Hz 3phase HP 2
480V 60Hz 3phase A 3.4
600V 60Hz 3phase HP 3
12/28/2018 Eaton 277436 ED2018 V51.0 EN 5 / 13