Datasheet

Interference immunity to EN 60947-1
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
200 V
208 V
HP 15
230 V
240 V
HP 20
460 V
480 V
HP 40
575 V
600 V
HP 50
Single-phase
115 V
120 V
HP 3
230 V
240 V
HP 10
General use A 80
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 10
max. Fuse A 250
max. CB A 250
480 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 250/150 Class J
SCCR (CB) kA 65
max. CB A 100
600 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 250/150 Class J
SCCR (CB) kA 30
max. CB A 250
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3phase, 277V 60Hz 1phase A 79
600V 60Hz 3phase, 347V 60Hz 1phase A 79
Incandescent Lamps (Tungsten)
480V 60Hz 3phase, 277V 60Hz 1phase A 74
600V 60Hz 3phase, 347V 60Hz 1phase A 74
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase A 79
600V 60Hz 3phase, 347V 60Hz 1phase A 79
Elevator Control
200V 60Hz 3phase HP 10
200V 60Hz 3phase A 32.2
240V 60Hz 3phase HP 15
240V 60Hz 3phase A 42
480V 60Hz 3phase HP 30
480V 60Hz 3phase A 40
600V 60Hz 3phase HP 40
600V 60Hz 3phase A 41
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 50
Heat dissipation per pole, current-dependent P
vid
W 3.3
12/28/2018 Eaton 278009 ED2018 V51.0 EN 5 / 13