Datasheet
Rated operational voltage U
e
V AC 500
Safe isolation to EN 61140
between coil and auxiliary contacts V AC 400
between the auxiliary contacts V AC 400
Rated operational current A
Conventional free air thermal current, 1 pole
Open
at 60 °C I
th
A 16
AC-15
220 V 230 V 240 V I
e
A 4
380 V 400 V 415 V I
e
A 4
500 V I
e
A 1.5
DC current
DC L/R ≦ 15 ms
Contacts in series: A
1 24 V A 10
1 60 V A 6
1 110 V A 3
1 220 V A 1
DC-13 (6xP)
24 V I
e
A 2.5
60 V I
e
A 1
110 V I
e
A 0.5
220 V I
e
A 0.25
Control circuit reliability Failure rate λ
<10
-8
, < one failure at 100 million operations
(at U
e
= 24 V DC, U
min
= 17 V, I
min
= 5.4 mA)
Component lifespan
at U
e
= 230 V, AC-15, 3 A Operations
x 10
6
1.3
Short-circuit rating without welding
max. fuse A gG/gL 10
Terminal capacity control circuit cables
Solid
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
mm
2
1 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded AWG 18 – 14
Tool
Control circuit cables
Standard screwdriver mm 0.6 x 3.5
Rating data for approved types
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 1
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 4
Heat dissipation per pole, current-dependent P
vid
W 0.16
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
12/28/2018 Eaton 277751 ED2018 V51.0 EN 2 / 6