Datasheet

Safe isolation to EN 61140
between coil and auxiliary contacts V AC 400
between the auxiliary contacts V AC 400
Rated operational current A
Conventional free air thermal current, 1 pole
Open
at 60 °C I
th
A 16
AC-15
220 V 230 V 240 V I
e
A 4
380 V 400 V 415 V I
e
A 4
500 V I
e
A 1.5
DC current
DC L/R ≦ 15 ms
Contacts in series: A
1 24 V A 10
1 60 V A 6
1 110 V A 3
1 220 V A 1
DC-13 (6xP)
24 V I
e
A 2.5
60 V I
e
A 1
110 V I
e
A 0.5
220 V I
e
A 0.25
Control circuit reliability Failure rate λ
<10
-8
, < one failure at 100 million operations
(at U
e
= 24 V DC, U
min
= 17 V, I
min
= 5.4 mA)
Component lifespan
at U
e
= 230 V, AC-15, 3 A Operations
x 10
6
1.3
Short-circuit rating without welding
max. fuse A gG/gL 10
Rating data for approved types
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 1
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 4
Heat dissipation per pole, current-dependent P
vid
W 0.16
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 60
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
12/28/2018 Eaton 106112 ED2018 V51.0 EN 2 / 4