Technical Bulletin

EtherNet/IP On-Board Communications
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com 65
Input Instances
Assembly Instance 70
Table 89. Instance 70 (Input) Length = 4 Bytes
Assembly Instance 71
Table 90. Instance 71 (Input) Length = 4 Bytes
1
Refer “State transition diagram”, provided under “Control Supervisor Object” and “Drive State
table specified at end of “Input Instances” section.
Assembly Instance 73
Table 91. Instance 73 (Input) Length = 6 Bytes
1
Refer “State transition diagram”, provided under “Control Supervisor Object” and “Drive State
table specified at end of “Input Instances” section.
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 Running1 Faulted
1
2 Speed Actual (Low Byte), rpm
3 Speed Actual (High Byte), rpm
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 AtReference RefFromNet CtrlFromNet Ready Running2 Running1 Warning Faulted
1
Drive State
1
2 Speed Actual (Low Byte), rpm
3 Speed Actual (High Byte), rpm
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 AtReference RefFromNet CtrlFromNet Ready Running2 Running1 Warning Faulted
1
Drive State
1
2 Speed Actual (Low Byte), rpm
3 Speed Actual (High Byte), rpm
4 Torque Actual (Low Byte), Nm
5 Torque Actual (High Byte), Nm