Technical Bulletin
EtherNet/IP On-Board Communications
38 PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
PLC Programming
Process Data Out (Slave to Master)
The fieldbus master can read the frequency converter’s
actual values using process data variables. All PowerXL
applications use process data as follows.
Table 65. Process Data Out (Slave to Master)
The multipurpose control application has a selector parameter
for every process data. The monitoring values and drive
parameters can be selected using the ID number. Default
selections are as in the table above.
Data Value Unit Scale
Process data OUT 1 Output Frequency Hz 0.01 Hz
Process data OUT 2 Motor Speed rpm 1 rpm
Process data OUT 3 Motor Current A 0.1A
Process data OUT 4 Motor Torque % 0.1%
Process data OUT 5 Motor Power % 0.1%
Process data OUT 6 Motor Voltage V 0.1V
Process data OUT 7 DC link voltage V 1V
Process data OUT 8 Active Fault code — —