Technical Bulletin
PROFIBUS-DP External Communication Cards
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com 95
Fault Code Tracking
Table 118. Fault Codes
Generic Station Description (GSD) File
Please refer GSD file “019D0CFF.gsd”
Format Unsigned 8 0x00 Reserved Every slave shall at least support the data types Byte,
Word and Double Word (mandatory). Write requests
by the master preferable use the “correct” data types.
As substitute, Byte, Word, or Double Word are also
possible. The master shall be able to interpret all
values/data types.
0x01…0x36 Data types
0x37…0x3F Reserved
0x40 Zero
0x41 Byte
0x42 Word
0x43 Double word
0x44 Error
0x45…0xFF Reserved
No. of Values Unsigned 8 0x00…0xEA Quantity 0–234 Limitation because of 240 Bytes Data block size
(compatible with former PROFIdrive version 3.1.2).
0xEB…0xFF Reserved
Error Number Unsigned 16 0x0000… Error Numbers The more significant byte is reserved.
0x00FF
SN
Fault
Code Fault Possible Cause Correction measures
1 26 Device Change Option Board Changed Reset
2 27 Device Added Option Board Added
3 28 Device Removed Option Board Removed Reset
4 29 Device Unknown Unknown Option Board
5 35 Comm Bus Fault The data connection between the PROFIBUS
master and
Check the installation is correct.
6 56 OPT Card Fault Device option board or slot. The PROFIBUS
option board is broken.
Check the board and slot.
Table 117. Field Coding, continued
Field Data Type Values Comment