Technical Bulletin
BACnet MS/TP—On-Board Communication
74 PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
BACnet Overview
BACnet Technical Data
Protocol Implementation Conformance Statement (PICS)
Controller Profile
●
B-ASC
Segmentation Capability
●
Not supported
Data Link Layer and Routing Options
●
MS/TP Master Baud rates
(9600,19200,38400, 76800, 115200)
Character Sets Supported
●
UTF8
BIBBS Supported
●
Data Sharing
●
ReadProperty-B
●
WriteProperty-B
●
Device Management
●
Dynamic Device Binding–B
●
Dynamic Object Binding–B
●
DeviceCommunicationControl–B
●
ReinitializeDevice–B
●
Alarms and Events: Not supported
●
Schedules: Not supported
●
Trends: Not supported
●
Network Management: Not supported
Table 97. Supported Object Types and Properties Summery
Property
Device
Object Type
Analog Value
Object Type
Binary Value
Object Type
Object_Identifier ■■■
Object_Name ■■■
Object_Type ■■■
System_Status ■ ——
Vendor_Name ■ ——
Vendor_Identifier ■ ——
Model_Name ■ ——
Firmware_Revision ■ ——
Application_Software_Version ■ ——
Location — — —
Description ■■■
Protocol_Version ■ ——
Protocol_Revision ■ ——
Protocol_Services_Supported ■ ——
Protocol_Object_Types_supported ■ ——
Object_List ■ ——
Structured_Object_list — — —
Max_Apdu_Length_Accepted ■ ——
Segmentation_Supported ■ ——
Vt_Classes_Supported — — —
Active_Vt_Sessions — — —
Local_Time — — —
Local_Date — — —
Utc_Offset — — —
Daylight_Savings_Status — — —
Apdu_Segment_Timeout — — —