Technical Bulletin
Modbus TCP On-Board Communications
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com 17
Figure 11. Module and Network Status
Module Status Indications
Represents the state of the drive.
Table 34. Module Status LED Description
1
Flash rate is 1 flash per second.
Network Status Indications
Represents the state of the Ethernet port network interface.
Table 35. Network Status LED Description
1
Flash rate is 1 flash per second.
Indicator State Summary Meaning
Steady Off No power No power is supplied to the PowerXL.
Steady Green Device operational PowerXL is operating correctly.
Flashing Green
1
Standby PowerXL has not been configured.
Flashing Red
1
Minor fault PowerXL has detected a recoverable minor fault.
Note. An incorrect or inconsistent configuration would be considered a minor fault.
Also check that on clearing the fault, it turns off.
Steady Red Major fault PowerXL has detected a non-recoverable major fault.
Flashing Green/Red
1
Self-test PowerXL is performing its power up testing.
Module Status
Network Status
Indicator State Summary Meaning
Steady Off Not powered, no IP address PowerXL is powered off, or is powered on but with no IP address configured (Interface
Configuration attribute of the TCP/IP Interface Object).
Flashing Green
1
No connections An IP address is configured, but no CIP connections are established, and an Exclusive Owner
connection has not timed out.
Steady Green Connected At least one CIP connection (any transport class) is established, and an
Exclusive Owner connection has not timed out.
Flashing Red
1
Connection timeout PowerXL is powered on and an exclusive Owner connection has timed out. It returns to steady
green only when all timed out Exclusive Owner connections are established.
Steady Red Major fault PowerXL has detected a non-recoverable major fault.
Flashing Green/Red
1
Self-test PowerXL is performing its power up testing.