Quick Start Guide
Step 5—Standard Parameter List
20 PowerXL DG1 Series Adjustable Frequency Drives MN040012EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 16. Protections—P9
Code Parameter Min. Max. Unit Default ID Note
P9.1
12
4 mA Input Fault 0 306 0 = No Action
1 = Warning
2 = Warning: Previous Freq
3 = Warning: Preset Freq
4 = Fault
5 = Fault, Coast
P9.2
12
4 mA Fault Frequency 0.00 Par. P1.2 Hz 0.00 331
P9.3
12
External Fault 2 307 See P9.11
P9.4
12
Input Phase Fault 2 332 See P9.11
P9.5
12
Uvolt Fault Response 2 330 See P9.11
P9.6
12
Output Phase Fault 2 308 See P9.11
P9.7
12
Ground Fault 2 309 See P9.11
P9.8
12
Motor Thermal Protection 2 310 See P9.11
P9.9
2
Motor Thermal F0 Current 0.0 150.0 % 40.0 311
P9.10
2
Motor Thermal Time 1 200 min 12 312
P9.11
12
Stall Protection 0 313 0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
P9.12
2
Stall Current Limit 0.1 Active Motor
Nom I*2
A Active Motor Nom
I*13/10
314
P9.13
2
Stall Time Limit 1.0 120.0 s 15.0 315
P9.14
2
Stall Frequency Limit 1.00 Par. P1.2 Hz 25.00 316
P9.15
12
Underload Protection 0 317 See P9.11
P9.16
2
Underload Fnom Torque 10.0 150.0 % 50.0 318
P9.17
2
Underload F0 Torque 5.0 150.0 % 10.0 319
P9.18
2
Underload Time Limit 2.00 600.00 s 20.00 320
P9.19
12
Thermistor Fault Response 2 333 See P9.11
P9.20
2
Line Start Lockout 2 750 0 = Disabled, No Change
1 = Enable, No Change
2 = Disabled, Changed
3 = Enable, Changed
P9.21
12
Fieldbus Fault Response 2 334 See P9.11
P9.22
12
OPTCard Fault Response 2 335 See P9.11
P9.23
12
Unit Under Temp Prot 2 1564 See P9.11
P9.24
2
Wait Time 0.10 10.00 s 0.50 321
P9.25
2
Trail Time 0.00 60.00 s 30.00 322
P9.26
2
Start Function 0 323 0 = Ramp
1 = Flying Start
2 = Start
P9.27
2
Undervoltage Attempts 0 10 1 324
P9.28
2
Overvoltage Attempts 0 10 1 325
P9.29
2
Overcurrent Attempts 0 3 1 326
P9.30
2
4 mA Fault Attempts 0 10 1 327
P9.31
2
Motor Temp Fault Attempts 0 10 1 329