Quick Start Guide

Step 5Standard Parameter List
18 PowerXL DG1 Series Adjustable Frequency Drives MN040012EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P5.15
2
Temp Limit Supv 0 165 See P5.11
P5.16
2
Temp Limit Supv Val –10.0 75.0 °C 40.0 166
P5.17
2
Power Limit Supv 0 167 See P5.11
P5.18
2
Power Limit Supv Val 0.0 200.0 % 0.0 168
P5.19
2
AI Supv Select 0 170 0 = AI1
1 = AI2
P5.20
2
AI Limit Supv 0 171 See P5.11
P5.21
2
AI Limit Supv Val 0.00 100.00 % 0.00 172
P5.30 RO1 On Delay 0 320 s 0 2111
P5.31 RO1 Off Delay 0 320 s 0 2112
P5.32 RO2 On Delay 0 320 s 0 2113
P5.33 RO2 Off Delay 0 320 s 0 2114
P5.34 RO3 On Delay 0 320 s 0 2115
P5.35 RO3 Off Delay 0 320 s 0 2116
P5.36 RO3 Reverse 0 1 0 2117 0 = Not Inverted
1 = Inverted
Table 14. Drive Control—P7
Code Parameter Min. Max. Unit Default ID Note
P7.1
2
Remote 2 Control Place 1 138 See P1.11
P7.2
12
Remote 2 Reference 7 139 See P1.12
P7.3
2
Keypad Reference Par. P1.1 Par. P1.2 Hz 0.00 141
P7.4
2
Keypad Direction 0 116 0 = Forward
1 = Reverse
P7.5
2
Keypad Stop 1 114 0 = Enabled-Keypad Operation
1 = Always Enabled
P7.6
2
Jog Reference Par. P1.1 Par. P1.2 Hz 0.00 117
P7.9
2
Start Mode 0 252 0 = Ramp
1 = Flying Start
P7.10
2
Stop Mode 1 253 0 = Coasting
1 = Ramp
P7.11
2
Ramp 1 Shape 0.0 10.0 s 0.0 247
P7.12
2
Ramp 2 Shape 0.0 10.0 s 0.0 248
P7.13
2
Accel Time 2 0.1 3000.0 s 10.0 249
P7.14
2
Decel Time 2 0.1 3000.0 s 10.0 250
P7.15
2
Skip F1 Low Limit 0.00 Par. P7.16 Hz 0.00 256
P7.16
2
Skip F1 High Limit Par. P7.15 400.00 Hz 0.00 257
P7.17
2
Skip F2 Low Limit 0.00 Par. P7.18 Hz 0.00 258
P7.18
2
Skip F2 High Limit Par. P7.17 400.00 Hz 0.00 259
P7.19
2
Skip F3 Low Limit 0.00 Par. P7.20 Hz 0.00 260
P7.20
2
Skip F3 High Limit Par. P7.19 400.00 Hz 0.00 261
P7.21
2
Prohibit Accel/Decel Ramp 0.1 10.0 1.0 264
Table 13. Digital Output—P5, continued
Code Parameter Min. Max. Unit Default ID Note