Quick Start Guide
Step 5—Standard Parameter List
PowerXL DG1 Series Adjustable Frequency Drives MN040012EN—March 2014 www.eaton.com 17
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 13. Digital Output—P5
Code Parameter Min. Max. Unit Default ID Note
P5.1
2
DO1 Function 1 151 0 = Not Used
1 = Ready
2 = Run
3 = Fault
4 = Fault Invert
5 = Warning
6 = Reversed
7 = At Speed
8 = Zero Frequency
9 = Freq Limit 1 Superv
10 = Freq Limit 2 Superv
13 = Overheat Warning
14 = Overcurrent Regular
15 = Overvoltage Regular
16 = Undervoltage Regular
17 = 4 mA Ref Fault/Warning
20 = Torq Limit Superv
21 = Ref Limit Superv
22 = Control from I/O
23 = Un-Requested Rotation
Direction
24 = Thermistor Fault Output
27 = Ext Fault/Warning
28 = Remote Control
29 = Jog Speed Select
30 = Motor Therm Protection
31 = FB Digital Input 1
32 = FB Digital Input 2
33 = FB Digital Input 3
34 = FB Digital Input 4
36 = TC1 Status
37 = TC2 Status
38 = TC3 Status
39 = In E-Stop
40 = Power Limit Superv
41 = Temp Limit Superv
42 = Analog Input Superv
P5.2
2
RO1 Function 2 152 See P5.1
P5.3
2
RO2 Function 3 153 See P5.1
P5.4
2
RO3 Function 7 538 See P5.1
P5.5
2
Freq Limit 1 Supv 0 154 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
P5.6
2
Freq Limit 1 Supv Val 0.00 Par. P1.2 Hz 0.00 155
P5.7
2
Freq Limit 2 Supv 0 157 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
P5.8
2
Freq Limit 2 Supv Val 0.00 Par. P1.2 Hz 0.00 158
P5.9
2
Torque Limit Supv 0 159 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
P5.10
2
Torque Limit Supv Val –300.0 300.0 % 100.0 160
P5.11
2
Ref Limit Supv 0 161 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
P5.12
2
Ref Limit Supv Val 0.00 Par. P1.2 Hz 0.00 162