Installation Manual

Appendix D—Safety Instructions for UL and cUL
68 DG1 Series VFD MN040002EN—March 2014 www.eaton.com
For 230V Drive Series, required grounding wire torque,
type and size range are listed as below:
Table 44. Required Line and Motor Wire Torque (230V)
Catalog
Number Terminal Type
Required
Torque
(in-lb)
Required
Wire
Range
FR1
DG1-323D7xx-xxxx Grounding terminal 10 14–10 AWG
DG1-324D8xx-xxxx 10 14–10 AWG
DG1-326D6xx-xxxx 10 14–10 AWG
DG1-327D8xx-xxxx 10 14–10 AWG
DG1-32011xx-xxxx 10 14–10 AWG
FR2
DG1-32012xx-xxxx Grounding terminal 10 12–6 AWG
DG1-32017xx-xxxx 10 10–6 AWG
DG1-32025xx-xxxx 10 10–6 AWG
FR3
DG1-32031xx-xxxx Grounding terminal 10 10–4 AWG
DG1-32048xx-xxxx 10 10–4 AWG
FR4
DG1-32061xx-xxxx Grounding terminal 14 8–1/0 AWG
DG1-32075xx-xxxx 14 6–1/0 AWG
DG1-32088xx-xxxx 14 6–1/0 AWG
FR5
DG1-32114xx-xxxx Grounding terminal 35 6 AWG–
250 kcmil
DG1-32143xx-xxxx 35 6 AWG–
250 kcmil
DG1-32170xx-xxxx 35 4 AWG–
250 kcmil