Appendix D—Safety Instructions for UL and cUL
66 DG1 Series VFD MN040002EN—March 2014 www.eaton.com
●
230V Drive Series are suitable for use on a circuit capable
of delivering not more than 100,000 rms symmetrical
amperes, 240 volts maximum when protected by UL and
cUL/CSA Recognized Class T fuse with an A.I.C. rating of
100 kA minimum. Refer to the following information for
recommended fuse ratings. See Table 40.
Table 40. Fuse Ratings—230V Drive Series
Field Wiring
●
The field installed conductors for this drive should be 75°C
copper wire only
●
The enclosure openings provided for conduit connections
in the field shall be closed by UL Listed conduit fittings
with same type rating as the enclosure (Type 1/Type 12)
Line and Motor Wiring
●
For 400V Drive Series, required line and motor wire torque,
type and size range are listed in Table 41
Table 41. Required Line and Motor Wire Torque (400V)
Frame Size
Catalog
Number Fuse Rating
1 DG1-323D7xx-xxxx 600V, 10A
DG1-324D8xx-xxxx 600V, 10A
DG1-326D6xx-xxxx 600V, 10A
DG1-327D8xx-xxxx 600V, 15A
DG1-32011xx-xxxx 600V, 15A
2 DG1-32012xx-xxxx 600V, 20A
DG1-32017xx-xxxx 600V, 30A
DG1-32025xx-xxxx 600V, 35A
3 DG1-32031xx-xxxx 600V, 60A
DG1-32048xx-xxxx 600V, 80A
4 DG1-32061xx-xxxx 600V, 100A
DG1-32075xx-xxxx 600V, 110A
DG1-32088xx-xxxx 600V, 125A
5 DG1-32114xx-xxxx 600V, 175A
DG1-32143xx-xxxx 600V, 200A
DG1-32170xx-xxxx 600V, 250A
Catalog
Number Terminal Type
Required
Torque
(in-lbs)
Required
Wire
Range
FR1
DG1-342D2xx-xxxx L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
5–7 14–10 AWG
DG1-343D3xx-xxxx 5–7 14–10 AWG
DG1-344D3xx-xxxx 5–7 14–10 AWG
DG1-345D6xx-xxxx 5–7 14–10 AWG
DG1-347D6xx-xxxx 5–7 14–10 AWG
DG1-349D0xx-xxxx 5–7 14–10 AWG
FR2
DG1-34012xx-xxxx L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
15.6 12–6 AWG
DG1-34016xx-xxxx 15.6 10–6 AWG
DG1-34023xx-xxxx 15.6 8–6 AWG
FR3
DG1-34031xx-xxxx L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
40 8–2 AWG
DG1-34038xx-xxxx 40 6–2 AWG
DG1-34046xx-xxxx 40 4–2 AWG
FR4
DG1-34061xx-xxxx L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
95 4–1/0 AWG
DG1-34072xx-xxxx 95 3–1/0 AWG
DG1-34087xx-xxxx 95 1–1/0 AWG
FR5
DG1-34105xx-xxxx L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
354 2/0 AWG–
350 kcmil
DG1-34140xx-xxxx 354 3/0 AWG–
350 kcmil
DG1-34170xx-xxxx 354 250–350 kcmil
All Frames Sizes (FR1–FR5)
All models Control terminal
block
4.5
28~12 (Sol) AWG
30~12 (Str) AWG