DG1 Series VFD MN040002EN—March 2014 www.eaton.com 45
Ambient conditions,
continued
Shock:
●
ISTA 1 A
●
EN 60068-2-27
Storage and shipping: maximum 15 g, 11 ms (in package)
Overvoltage Overvoltage Category III
Pollution degree Pollution Degree 2
Enclosure class IP21/Type 1 standard in entire kW/hp range
IP54/Type 12 option
Note: Keypad or keypad hole plug required to be mounted in drive for IP54/Type 12 rating
Immunity Fulfills EN 61800-3 (2004), first and second environment
MTBF FR1: 165,457 hours
FR2: 134,833 hours
FR3: 102,515 hours
FR4: 121,567 hours
FR5: 108,189 hours
FR6: Available in 2015
Standards Safety UL 508C, CSA C22.2 No. 274-13 and EN 61800-5-1
EMC +EMC2: EN 61800-3 (2004), Category C2
The drive can be modified for IT networks and corner grounding TN system
Electrostatic discharge Second environment, IEC 61000-4-2, 4 kV CD or 8 kV AD, Criterion B
Fast transient burst Second environment, IEC 61000-4-4, 2 kV/5 kHz, Criterion B
Dielectrical strength Primary to secondary: 3600 Vac/5100 Vdc
Primary to earth: 2000 Vac/2828 Vdc
Approvals EN 61800-5-1 (2007), CE, UL and cUL (see nameplate for more detailed approvals)
Fieldbus connections EtherNet/IP, Modbus
®
TCP, Modbus RTU, BACnet
Safety/protections Overvoltage protection Yes
Overvoltage trip limit 240V drives: 456V
480V drives: 911V
Undervoltage protection Yes
Undervoltage trip limit 240V drives: 211V
480V drives: 370V
Earth fault protection Yes
Input phase supervision Yes
Motor phase supervision Yes
Overcurrent protection Yes
Unit overtemperature protection Yes
Motor overload protection Yes
Motor stall protection Yes
Motor underload protection Yes
DC bus overvoltage control Yes
Short-circuit protection of 24V
reference voltages
Yes
Surge protection Yes (differential mode 2 kV; common mode 4 kV)
Common coated boards Yes (prevents corrosion)
Table 28. PowerXL Series—DG1, continued
Attribute Description Specification