Table 28. PowerXL Series—DG1
Attribute Description Specification
Input ratings Input voltage U
in
208V to 240V, 380V to 500V, 525V to 600V, –15 to 10%
Input frequency 50 Hz to 60 Hz (variation up to 45 Hz to 66 Hz)
Connection to power Once per minute or less
Starting delay 3 s (FR1 to FR2), 4 s (FR3), 5 s (FR4), 6 s (FR5)
Short-circuit withstand rating 100 kAIC
Output ratings Output voltage 0 to U
in
Continuous output current IL: ambient temperature maximum 40°C, up to 60°C with derating, overload 1.1 x IL (1 min./10 min.)
IH: ambient temperature maximum 50°C, up to 60°C with derating, overload 1.5 x IH (1 min./10 min.)
Overload current 150% respectively 110% (1 min./10 min.)
Initial output current 200% (2 s/20 s)
Output frequency 0–400 Hz (standard)
Frequency resolution 0.01 Hz
Control characteristics Control methods Frequency control
Speed control
Open-loop speed control
Open-loop torque control
Switching frequency Range:
FR1–3: 1 kHz to 12 kHz
FR4–5: 1 kHz to 10 kHz
Defaults:
FR1–3: 4 kHz (IH), 6 kHz (IL)
FR4–5: 3.6 kHz
Automatic switching frequency derating in case of overload.
Frequency reference Analog input: resolution 0.1% (10-bit), accuracy +1%
Panel reference: resolution 0.01 Hz
Field weakening point 20 Hz to 400 Hz
Acceleration time 0.1 s to 3000 s
Deceleration time 0.1 s to 3000 s
Braking torque DC brake: 30% x Motor Rated Torque (Tn) (without brake chopper)
Dynamic braking (with optional brake chopper using an external brake resistor):
100% continuous maximum rating
Ambient conditions Ambient operating temperature –10°C (no frost) to +50°C, up to +60°C with derating (CT)
–10°C (no frost) to +40°C, up to +55°C with derating (VT)
Storage temperature –40°C to +70°C
Relative humidity 0–95% RH, noncondensing, non-corrosive
Air quality:
Chemical vapors
Mechanical particles
Tested according to IEC 60068-2-60 Test Key:
Flowing mixed gas corrosion test, Method 1 (H2S [hydrogen sulfide] and SO2 [sulfur dioxide])
Designed according to:
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
Altitude 100% load capacity (no derating) up to 3280 ft (1000 m); 1% derating for each 328 ft (100 m) above
3280 ft (1000 m); max. 9842 ft (3000 m) (2000 m for corner grounded earth main systems)
Vibration:
EN 61800-5-1
EN 60668-2-6
5–150 Hz
Displacement amplitude: 1 mm (peak) at 5 Hz to 15.8 Hz (FR1–FR5)
Maximum acceleration amplitude: 1g at 15.8 Hz to 150 Hz (FR1–FR5)